>Here I have presented my problem in different way. Suppose I have a fan of
>20000 CFM air capacity.
That means your fan will move 20000 CFM without a restriction either on
the inlet or outlet. If you put short inlet or outlet ducts that are the
same diameter as the fan, you'll get your 20000 CFM. The minute you add
some restriction, the pressure at the fan outlet goes up correspondingly
and the flow rate goes down according to the delivery curve.