Glenn Dillon <glenn.dillon@task-consultancy.co.nz> wrote: Hitesh, assume these
are butt weld fittings. Fitting to fitting is
preferred but where not possible I work on minimum pup spool distance of 50
mm to allow for weld effected zone and weld efficiency. Haven't had any
failures yet. With steam, elbows can be highly stressed and its best to
ovoid short pipe sections and layout distribution to allow fitting to
fitting.
Hope these comments of some help. Best regards Glenn
-----Original Message-----
From: Ashok Dani [mailto:ashokdani@tatachem.tata.com]
Sent: Friday, March 22, 2002 4:29 PM
To: 'pipingdesign@yahoogroups.com'
Subject: [PipingDesign] Minimum distance between Fittings
Importance: High
> What is the minimum distance required between Bend-Tee or Tee-Tee for
> Steam
> line or as per B31.1?
> Thanks in advance
> Hitesh