Hello Friends,
Use of trunion on elbow is generally accepted practice. Some companies do not allow at all and some companies do allow on conditional basis.
You can use it for temp. below 150 deg C (No problem at all.) But it's not good to use it above 150 deg C. The reason is simple that we can take advantage of flexibility associated with the elbow in stress analysis. Also I would suggest to avoid it above 60 deg C for Stainless Steel and Alloy Steel lines.
Better go for a support at the pipe (horizontal or vertical as well).
Thanks and regards.
Tushar Zope
Piping Engineer
Foster Wheeler Eastern Pte. Ltd, Singapore
Ph: 6890 0837 Fax: 6223 2989
Disclaimer
'The information contained in this email and the files transmitted with it are
confidential and intended only for the use of the individual or entity to whom
they are addressed. If you have received this message in error, please
immediately notify the sender and delete the mail. The views or opinions
presented in this email are those of the author and do not necessarily represent
those of the company. The recipient should check this email and any attachments
for the presence of viruses. Foster Wheeler Eastern Pte Ltd accepts no liability
for any damage caused by any virus transmitted by this email.'
____________________Reply Separator____________________Subject: Re: [PipingDesign] Trunnion on an Elbow Author: <a href="/group/PipingDesign/post?postID=Y5fgltOWZD8zNSne_jWP8avp6R_oaygRocXLLMurrWqkKJthna_QhPyiERFOFUtBeFI22PP79wQKpKzJYQ">Sachin_Bapat@ril.com</a> Date: 9/7/02 8:46 AM
If you go through piping design books you will find that
trunnion on elbow
reduces the flexiblity of trunnion & also it modifies the value
of sif &
flexibility factor . piping design book (M W kellogg) chapter 4
-local
components expilicitly derives relation for the same, thats
why most of
design companies dont prefer trunnion on elbows & use of pads
for trunnion
on elbow is highly discarded as all these reduce flexibility of
trunnion ,
which may be of concern in rigid layouts
hope this answers your query.
regards
sachin
Yahoo! Groups Sponsor
ADVERTISEMENT
<<a href="http://rd.yahoo.com/M=229441.2336363.3766536.2225242/D=egroupw">http://rd.yahoo.com/M=229441.2336363.3766536.2225242/D=egroupw</a>
eb/S=1705083319:HM/A=1189560/R=0/*<a href="http://www.bmgmusic.com/acq/e">http://www.bmgmusic.com/acq/e</a>
e/q6/enroll/mhn/10/>
Texas Flange - a good source for information on industrial
flanges, all they ask is for referrals for designs they help
with.
877-610-8924.
www.texasflange.com
=====================================================
unsubscribe: <a href="/group/PipingDesign/post?postID=YOu5XfabQh73IHpw7BnNVIVuobE8F5pV6cUYnHI63UXURRvDn1FsJSWgS6T7U7xDONTraYGJjRIvvwZvI9eS4Rk5EJPAix9TvWhB2pvfa_n-L3s">PipingDesign-unsubscribe@yahoogroups.com</a>
Your use of Yahoo! Groups is subject to the Yahoo! Terms of
Service <http://docs.yahoo.com/info/terms/>.
Received on Mon Sep 09 06:52:00 2002
This archive was generated by hypermail 2.1.8 : Tue Mar 04 2008 - 11:40:24 EST