Column Reboiler problem

From: <Tanmoy>
Date: Thu Sep 12 2002 - 07:54:00 EDT


Hi all

This is a problem observed and raised by one of my friend. My views are as below

Information is not complete. Further information like full detail of the column at least the distances of the nozzles from bottom tangent line of the column is required.

However it looks like it is not a stress problem as there is mismatch of two nozzles. If it was a stress problem both the nozzles should have deflected same way and there shouldn't have been any relative displacement. Possible things are

  1. the nozzles were offset at the beginning itself and forcefully joined by some tricks. (most likely)
  2. the tower and the reboiler were not at the same temperature which is less likely.

Am I correct? What do you think?

Thanks

Tanmoy Saha
Kellog Brown & Root, Singapore.
Ph. 6422 2535
Email. <a href="/group/PipingDesign/post?postID=gQyqA8esAnglXvW0w_Fxr7Ta9gOt5tvCMikrmZayv85J5tX-bLH2sLMklED1vMYo-_hIjOh6E2PqDvLmOkvljjteLZiwwQ">Tanmoy.Saha@Halliburton.com</a>

Problem:

COLUMN

              Reboiler
                                                       80" connection






Reboiler
Flange

4 Lugs
2 Springs

   per lug

There is a column with a reboiler connection of 80" size. The reboiler is supported on 4 lugs and there are 2 F type springs below each lug. Each spring takes a load of about 10 tonnes. The reboiler is very heavy. The reboiler is supported on a separate concrete structure. After about 8 years of operation client found out that the 80" connection nozzle flange and the reboiler body flange were leaking. So to replace the gaskets the reboiler was disconnected at the the 80" nozzle flange and the body flange. When they were refitting the removed part of the reboiler back to the original position, they first connected the 80" nozzle flange. Then they found out that there was 10 mm gap between the two body flanges. Nobody is able to guess what happened. The lugs are still touching the spring load flange. The pointer on the flange is at topmost position and not at center.
There are 30" piping connections on the downward part of the reboiler.

Can u suggest any reasons what could have gone wrong ??

[Non-text portions of this message have been removed] Received on Thu Sep 12 07:54:00 2002

This archive was generated by hypermail 2.1.8 : Tue Mar 04 2008 - 11:40:24 EST