Re: Hydro Test Pressure

From: <benj>
Date: Thu Sep 11 2003 - 06:41:00 EDT


Chapter VI of B31.3 – "… each piping shall be tested to ensure tightness."
The Code further stated "… the test pressure maybe reduced to the max. pressure that will not exceed the yield strength." This statement appeared twice in Section 345.

The posting on this threads makes it appears that performing hydro on newly installed process piping during the pre-commissioning is a complex and difficult task – it is not. If the hydro test plan has well thought of then the rigorous detail of analysis previously stated is not necessary. Basically if one has develop the hydro test diagram then it is sufficient to evaluate systematically the limiting components of the piping system (together with the line designation table) that will dictate the hydro test pressure, the filling/drain point, pipe support requirements, the blind location and even the need to install a pressure relieving device.

Following the threads, it looks like that the end0user is expecting that the hydro will sort of provide a guarantee of safety. Not so. Piping that pass the hydro can still fail in service – it hardly qualify as a proof test. Its very purpose is to reveal design inadequacy and flanges/weld/joint leaks.

Received on Thu Sep 11 06:41:00 2003

This archive was generated by hypermail 2.1.8 : Tue Mar 04 2008 - 11:40:29 EST