DEEPAK - My understanding is that for compliance with B31.3, all systems require a flexibility analysis unless the system duplicates a successfully operating system, can be judged adequate by comparison with previously analyzed system or are within the limits of Paragraph 319.4.1.
Ken A. Nisly-Nagele, P.E.
Project Engineer, Mechanical
Applied Engineering Services, Inc.
7999 Knue Road
Indianapolis, IN 46250
317-585-8920
-----Original Message-----
From: GET Mithapur [mailto:getuser@tatachemicals.com]
Sent: Friday, July 16, 2004 6:02 AM
To: 'pipingdesign@yahoogroups.com'
Subject: [PipingDesign] When Flexibility Analysis is Needed?
Dear All,
Can anybody tell us when Piping Flexibility Analysis is needed? I have referred B.31.3 & B31.1 (clause 319.4.1 & 119.7.1) but not reached any clear conclusion.
What are criteria involved for Piping Stress Analysis. Are there any minimum requirements to be considered while deciding for Flexibility Analysis?
DEEPAK
Yahoo! Groups Links Received on Fri Jul 16 09:32:00 2004
This archive was generated by hypermail 2.1.8 : Mon Oct 27 2008 - 20:24:04 EDT