RE: Question on Wafer NRV installation

From: <Pankaj.Mandal@fluor.com>
Date: Tue Nov 02 2004 - 23:10:00 EST


Erik,

A small query:
".........a nozzle check valve closes much faster then a duo-check valve......"

I my opinion, a fast closing valve will induce higher dynamic shock load. You can have a quick reference to Joukowski's Law for details.

Though I have never used a nozzle type check valve and I hence not aware of the characteristics, I have seem many successful installation of wafer type check valves without major problems with respect to operations.

Regards,
Pankaj.

"Erik Scheir" <erik.scheir@pandora.be> 11/02/04 11:11 PM
Please respond to PipingDesign

         To:     <PipingDesign@yahoogroups.com>
         cc:
         Subject:        RE: [PipingDesign] Question on Wafer NRV installation
.

Hello Steve,

I have a lot of (bad) experience with wafer check valves with respect to waterhammer.

It is not that I blame a check valve (in general) to cause waterhammer, but
some do and all depends ont the dynamic characteristic of the valve.

I always use Nozzle Check valves and I can show some graphs to explain the difference between a nozzle check valve and a wafer check valve but I don't
know were I can send those graphs.

All check valves closes under reverse flow but a nozzle check valve closes
much faster then a duo-check valve so the reverse velocity is much lower and
so is the pressure rise.

The ideal check valve is a diode but ideal doesn't exist,

Cheers,

Erik


Van: Steve McKenzie [mailto:mechproj@xtra.co.nz] Verzonden: dinsdag 2 november 2004 12:30 Aan: <a href="/group/PipingDesign/post?postID=vt1huCdm3BM2HyIX6A3hdlDuer24WxLW6UTJvdbDXWIK7ZIdMMjBv6x5irvrqe5SWt2pd94trp_3s_Zs851uX9IkpLcSYA">PipingDesign@yahoogroups.com</a> Onderwerp: RE: [PipingDesign] Question on Wafer NRV installation

Hello Erik

in my opinion, it is unfair to blame a check valve for causing water hammer. The check valve merely closes under reverse flow, or, if you are lucky, at zero flow. That is what it is designed to do. It is the pressure of the water after the check valve has (nearly)closed that causes the damage. How can you blame the check valve for that? In my opinion, check valves work just fine. It is just that they also double as surge (water hammer) control devices; often without the "designer" even being aware of it.
For example, an undersized spring wafer check in a low pump inertia/high lift situation will close almost immediately after its pump stops. There will be no appreciable flow reversal so the water column will just "sit down" and the wafer will see about twice (conservatively) the normal operating head. The problem is that the return springs on the wafers are probably made of shit metal amd will set so reverse flow is the only available force that will close the wafers. So in new condition the wafer check valve works fine, but in worn condition (no springs) reverse flow must be allowed for in the design.
Now take the humble swing check valve. It has no springs, requires reverse flow to close, costs a fortune, and is sold by the thousand. It also has a spindle.
The worst thing you can do with a swing check is to oversize it. That means the disc is hanging, swinging in the breeze and wearing the spindle. Size them tight so the disc is banged hard against the stops. If you are worried about opex, do the sums; I have yet to see, this side of Mars, where a large check valve is economically justified. However, you can still overdo it. Many pumps have screamingly high discharge velocities; upwards of 7 m/s to keep the(casing) cost down. I try to limit the velocity that a check valve sees to around 4 m/s depending on spec and pennies; preferably around 2.5-3 m/s, but higher with a "smooth" design. Have yet to see a tilting disc design that pays its way, but I am used to cheap power costs, so will have to mend my ways as the oilwells dry up.

So Erik, if the function of a (wafer) check valve is to prevent reverse flow, and you recommend not using them, then you should see if you can suggest an alternative way of arresting reverse flow. Buggered if I know,but I hate the things. Check valves,that is.

Cheers

Steve

-----Original Message-----
From: Erik Scheir [mailto:erik.scheir@pandora.be] Sent: Tuesday, November 02, 2004 10:20 PM To: <a href="/group/PipingDesign/post?postID=vt1huCdm3BM2HyIX6A3hdlDuer24WxLW6UTJvdbDXWIK7ZIdMMjBv6x5irvrqe5SWt2pd94trp_3s_Zs851uX9IkpLcSYA">PipingDesign@yahoogroups.com</a> Subject: RE: [PipingDesign] Question on Wafer NRV installation

Hi Robin,

It is much better not to install Wafer Check Valves at all. They cause often waterhammer when there is a pumptrip.The reason for that is that they have a bad dynamic characteristic,

Best Regards,

Erik


Van: Robin Badcock [mailto:rbadcock@vision.net.au] Verzonden: zaterdag 30 oktober 2004 9:42 Aan: <a href="/group/PipingDesign/post?postID=vt1huCdm3BM2HyIX6A3hdlDuer24WxLW6UTJvdbDXWIK7ZIdMMjBv6x5irvrqe5SWt2pd94trp_3s_Zs851uX9IkpLcSYA">PipingDesign@yahoogroups.com</a> Onderwerp: [PipingDesign] Question on Wafer NRV installation

Hi Paul,

Looks like I must have some how upset our 900 or so members as I had recently posted a query with respect to correct wafer check valve installation and received no replies, or did it go off into cyber space.

Perhaps the query was inappropriate?

Cheers,

Robin

[Non-text portions of this message have been removed]



PipingOffice - Excel Spreadsheets for Piping Calculations
<a href="http://www.pipingoffice.us/">http://www.pipingoffice.us/</a> =========================================
Main site: <a href="http://www.pipingdesign.com">http://www.pipingdesign.com</a>

Yahoo! Groups Sponsor

ADVERTISEMENT
<<a href="http://us.ard.yahoo.com/SIG=129kv01nn/M=315388.5543472.6613714.3001176/">http://us.ard.yahoo.com/SIG=129kv01nn/M=315388.5543472.6613714.3001176/</a>
D=gr
oups/S=1705083319:HM/EXP=1099208578/A=2372354/R=0/SIG=12id813k2/*https:/ www.
orchardbank.com/hcs/hcsapplication?pf=PLApply&media=EMYHNL40F21004SS> click here

<<a href="http://us.adserver.yahoo.com/l?M=315388.5543472.6613714.3001176/D=group">http://us.adserver.yahoo.com/l?M=315388.5543472.6613714.3001176/D=group</a>
s/S=
:HM/A=2372354/rand=338185744>


Yahoo! Groups Links

[Non-text portions of this message have been removed]



PipingOffice - Excel Spreadsheets for Piping Calculations
<a href="http://www.pipingoffice.us/">http://www.pipingoffice.us/</a> =========================================
Main site: <a href="http://www.pipingdesign.com">http://www.pipingdesign.com</a>

Yahoo! Groups Links



PipingOffice - Excel Spreadsheets for Piping Calculations
<a href="http://www.pipingoffice.us/">http://www.pipingoffice.us/</a>


Main site: <a href="http://www.pipingdesign.com">http://www.pipingdesign.com</a>

Yahoo! Groups Sponsor

<<a href="http://us.ard.yahoo.com/SIG=129klc84t/M=281955.5530326.6602771.3001176/D=gr">http://us.ard.yahoo.com/SIG=129klc84t/M=281955.5530326.6602771.3001176/D=gr</a>
oups/S=1705083319:HM/EXP=1099481893/A=2343726/R=0/SIG=12ia956n7/*http:/clk.a tdmt.com/VON/go/yhxxxvon01900091von/direct/01/&time=1099395493930384>
<<a href="http://us.ard.yahoo.com/SIG=129klc84t/M=281955.5530326.6602771.3001176/D=gr">http://us.ard.yahoo.com/SIG=129klc84t/M=281955.5530326.6602771.3001176/D=gr</a>
oups/S=1705083319:HM/EXP=1099481893/A=2343726/R=1/SIG=12ia956n7/*http:/clk.a tdmt.com/VON/go/yhxxxvon01900091von/direct/01/&time=1099395493930384>

Get unlimited calls to
<<a href="http://us.ard.yahoo.com/SIG=129klc84t/M=281955.5530326.6602771.3001176/D=gr">http://us.ard.yahoo.com/SIG=129klc84t/M=281955.5530326.6602771.3001176/D=gr</a>
oups/S=1705083319:HM/EXP=1099481893/A=2343726/R=1/SIG=12ia956n7/*http:/clk.a tdmt.com/VON/go/yhxxxvon01900091von/direct/01/&time=1099395493930384>

U.S./Canada
<<a href="http://us.ard.yahoo.com/SIG=129klc84t/M=281955.5530326.6602771.3001176/D=gr">http://us.ard.yahoo.com/SIG=129klc84t/M=281955.5530326.6602771.3001176/D=gr</a>
oups/S=1705083319:HM/EXP=1099481893/A=2343726/R=1/SIG=12ia956n7/*http:/clk.a tdmt.com/VON/go/yhxxxvon01900091von/direct/01/&time=1099395493930384>

<<a href="http://view.atdmt.com/VON/view/yhxxxvon01900091von/direct/01/&time=10993954">http://view.atdmt.com/VON/view/yhxxxvon01900091von/direct/01/&time=10993954</a>
93930384>

<<a href="http://us.adserver.yahoo.com/l?M=281955.5530326.6602771.3001176/D=groups/S=">http://us.adserver.yahoo.com/l?M=281955.5530326.6602771.3001176/D=groups/S=</a>
:HM/A=2343726/rand=316795905>


Yahoo! Groups Links

[Non-text portions of this message have been removed]



PipingOffice - Excel Spreadsheets for Piping Calculations
<a href="http://www.pipingoffice.us/">http://www.pipingoffice.us/</a>


Main site: <a href="http://www.pipingdesign.com">http://www.pipingdesign.com</a>

Yahoo! Groups Links

--------------------------------------------------------------------------------\
---------------------

The information transmitted is intended only for the person or entity to which it is addressed and may contain proprietary, business-confidential and/or privileged material. If you are not the intended recipient of this message you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any action taken in reliance upon this message is prohibited. If you received this in error, please contact the sender and delete the material from any computer. Any views expressed in this message are those of the individual sender and may not necessarily reflect the views of the company.
--------------------------------------------------------------------------------\
-----------------------



[Non-text portions of this message have been removed] Received on Tue Nov 02 23:10:00 2004

This archive was generated by hypermail 2.1.8 : Tue Mar 04 2008 - 11:40:10 EST