Re: Reinforcement Pad Weep hole

From: <tomcruz55>
Date: Tue Sep 13 2005 - 01:53:00 EDT

Christopher Wright <chrisw@s...> wrote:

Actually they're used to give notice of leaks, which might take place
> during hydrotests. There's no way gas can be trapped inside during
> welding.


Ive witness it several times before. A RP was welded without the weep hole. Pad bulges. And we never plug (fitting) the weep holes.

Aside from venting gas during welding and providing you with a telltale  hole (notice of leaks as Chris said)udring operation, the weep hole is also use to perform a soap and bubble test (part of testing/exam prior to signoff). Received on Tue Sep 13 01:53:00 2005

This archive was generated by hypermail 2.1.8 : Mon Oct 27 2008 - 20:24:09 EDT