Dear Neeraj,
Velocity can be calculated by Q =A.V
For industrial gases :
Normally in Main Lines : 4-8 m/sec
Main distribution Lines : 8 -10 m/sec
Nozzle end velocity :15-40 m/sec depending upon various limitation
Best Reagrds
Khilawan Sahu
Message: 3
Date: Mon, 26 Sep 2005 07:51:33 -0700 (PDT) From: akif ozmen <maozmen@yahoo.com> Subject: Re: Pipe Velocity
Dear Neeraj,
For water :
Branchs at hospital heating system : 0,5-0,7 m/sec
Branchs at domestic heating system : 0,8-1 m/sec
Branchs at rooms : 1-1,5 m/sec
Main distribution lines : 1,5-2,0 m/sec
Main lines : 2,5-3,0 m/sec
Best Regards,
Akif Ozmen
-tiwarinj <ti-arinj@uniphos.com> wrote:
How do we decide the maximum velocity in a given diameter of pipe.
--
Regards
Neeraj Tiwari
MaxPro Dept.
b: 9879
isit:http://www.uplonline.com
Received on Tue Sep 27 00:01:00 2005