Sajit:
Your situation is unclear. Is your pipeline carrying a flammable gas, or a flammable mixture of gas? There is a big difference. Natural gas is flammable, but the gas is transmitted (piped) in nearly pure form, with no oxygen. As such it is not a flammable mixture. It is not ignitable. It is well over the Upper Flammability Limit (UFL).... it cannot burn nor sustain a flame. One is highly unlikely to transmit a flammable mixture of natural gas and air. Or for that matter, any flammable mixture. It's dangerous, costly, and there is seldom reason to do so. This being the case, the deflagration type is almost always used. Also be aware that the detonation type, for a fire internal to the pipe, is proportionately much larger. It has to drop the velocity down from sonic to sub-sonic. Because it is larger, it can be extremely expensive and difficult to mount (or find room to mount). Work with a knowledgeable supplier for guidance.
... Bruce D. Bullough ...
Lead Process Engineer
Foth Production Systems, LLC
8550 Hudson Boulevard North, Suite 100
Lake Elmo, MN 55042
Direct: +651-288-8598 Fax: +651-288-8551
<a href="http://www.foth.com">http://www.foth.com</a>
IMPORTANT NOTICE
This communication including any attachments, (E-mail) is confidential and
may be proprietary, privileged or otherwise protected from disclosure. If
you are not the intended recipient, please notify the sender, permanently
delete this E-mail from your system and destroy any copies. Any use of
the E-mail, including disclosure, distribution or replication, by someone
other than its intended recipient is prohibited.
This E-mail has the potential to have been altered or corrupted due to transmission or conversion. It may not be appropriate to rely upon this E-mail in the same manner as hard copy materials bearing the author's original signature or seal.
<a href="/group/PipingDesign/post?postID=r9kIWlZipk7uGzNR_SMfUMvvOlhxED9UgYPdGFUONeAfuYr0x5xRgSY0HcIvWLO1bssIzrdE2Kv7Wo1QiaM">sviswan@technip.com</a>
Sent by: <a href="/group/PipingDesign/post?postID=CpDd7bF0TraA3EzI39k5cZcP4g7QNl6lsiqBzC5PJ0zUvmXxD9TRRBiO94MM3Kmk5K69CJVJfoE__tsDL5KUfGbB1iSS">PipingDesign@yahoogroups.com</a>
02/07/2007 12:10 AM
Please respond to
<a href="/group/PipingDesign/post?postID=CpDd7bF0TraA3EzI39k5cZcP4g7QNl6lsiqBzC5PJ0zUvmXxD9TRRBiO94MM3Kmk5K69CJVJfoE__tsDL5KUfGbB1iSS">PipingDesign@yahoogroups.com</a>
To
<a href="/group/PipingDesign/post?postID=CpDd7bF0TraA3EzI39k5cZcP4g7QNl6lsiqBzC5PJ0zUvmXxD9TRRBiO94MM3Kmk5K69CJVJfoE__tsDL5KUfGbB1iSS">PipingDesign@yahoogroups.com</a>
cc
Subject
[PipingDesign] Flame Arrester
An end of line Flame arrester is to be provided on a vent line carrying flammable gas mixture.
To decide the type of the arrester, i.e. whether a deflagration or a
detonation type, it needs be decided on which side of the arrester is the
flash likely to occur. It seems to me that the what is normally provided
on
a vent line is an end of line deflagration type. This is based on the
consideration that the flash will occur on the outside. Is it that, there
is no likely hood of a flash occurring within the pipe, even though the
gas
mixture is a flammable one. The BS standard on this 12874 does not address
this. Neither does the literature that I saw at Elmac.
A detonation type is used to quench a flame front of sonic velocity
originating on the inside of the pipe. Where would this type be used, in
light of my query above, as to what would cause a flash to occur within
the
pipe.