On Jan 5, 2008, at 11:33 PM, sviswan@technip.com wrote:
> ASTM A672 is made from plates, therefore the allowable stress for
> the plate
> may be used.
If it's welded pipe the allowable stress will have to incorporate a
joint efficiency. Use the book allowables for welded pipe.
Christopher Wright P.E. |"They couldn't hit an elephant at <a href="/group/PipingDesign/post?postID=e6ZiEGwcDiei2v6HqS3dTQj2hPBvZJ3pEWgH4gVTjhhgmSw0iEe1QwKVcnuwVNOV-ADstuW6_XAbRQ">chrisw@skypoint.com</a> | this distance" (last words of Gen.
.......................................| John Sedgwick, Spotsylvania1864)