The failure is not due to flow disturbance if an SS pipe is used for
sea wtaer service. The concern is SCC. And the moment it starts,
failure is sure to happen - its just a matter of time. There are
other pipe material that is suitable for use for sea water
application . One is a cement lined CS pipe (coated and wrapped for
U/G application) or fiberglass pipe - both have a pretty good
service life.
- In PipingDesign@yahoogroups.com, "Arif Javed" <ajaved@...> wrote:
>
> How to you protect SS from chloride attack if used, without
coating,
> for Seawater?
>
>
>
> A J
>
> Lead Design Engineer
>
>
>
> _____
>
> From: <a href="/group/PipingDesign/post?postID=ItK4lhB0t4i4DhoAIHlNN09ocGxwsNFJDdVFDl0mxlOM75i-T9jKYi2r1TV9gqMlhKaCOM2Yi-xas9vp2VO5hQFdZR8Q">PipingDesign@yahoogroups.com</a>
[mailto:PipingDesign@yahoogroups.com]
> On Behalf Of Dacharaju Krishnamohan Rao
> Sent: 05 April 2007 07:19
> To: <a href="/group/PipingDesign/post?postID=ItK4lhB0t4i4DhoAIHlNN09ocGxwsNFJDdVFDl0mxlOM75i-T9jKYi2r1TV9gqMlhKaCOM2Yi-xas9vp2VO5hQFdZR8Q">PipingDesign@yahoogroups.com</a>
> Subject: Re: [PipingDesign] Re: Seawater cooling for power plant
>
>
>
> Use of SS316L and GRP for seawater service is also in practice.
> There is also an improvement of applying a Specail (paint) Coating
> inside
> on SS316L for an extended life where seawater flow disturbances
occur
> such
> as downstream of valves.
> regards,
> D.K.M.Rao.
>
>