RE: CS TO CPVC flange connection

From: <ed>
Date: Fri Oct 08 2004 - 15:45:00 EDT

Yes, definitely flat faced CS flanges to flat face PVC flanges.

If you use raised face CS flanges, the PVC flange will crack.

-----Original Message-----
From: Thomas Laupa [mailto:tlaupa@frii.com] Sent: Friday, October 08, 2004 12:34 PM
To: PipingDesign@yahoogroups.com
Subject: Re: [PipingDesign] CS TO CPVC flange connection

M Danish:

we generally use flat faced carbon steel flanges with a full face soft gasket (rubber or teflon). a raised face flange puts too much strain on

the flat faced PVC flange. and it's hard to get a standard gasket to seal
with the PVC flange. the PVC isn't much harder than the gasket. we also
are sure to use bolt kits designed for PVC with oversize washers.

hope this helps.

At 09:26 AM 10/8/2004 -0700, you wrote:

>Dear All,
>How can we join the CS pipe 2in to CPVC pipe using flange connection.
>Thanks,
>Md Danish
>
>__________________________________________________
>Do You Yahoo!?
>Tired of spam? Yahoo! Mail has the best spam protection around
>http://mail.yahoo.com
>
>[Non-text portions of this message have been removed]
>
>
>
>
>=========================================
>PipingOffice - Excel Spreadsheets for Piping Calculations
>http://www.pipingoffice.us/
>=========================================
>Main site: http://www.pipingdesign.com
>
>Yahoo! Groups Links
>
>
>
>

Thomas G Laupa PE
Senior Engineer - Nalco Company
Office Address: 1601 Diehl Road, Naperville, IL, 60563 Courier Address: 1003 Remington, Fort Collins, CO, 80524 970-227-5127
800-493-5009 fax



PipingOffice - Excel Spreadsheets for Piping Calculations http://www.pipingoffice.us/

Main site: http://www.pipingdesign.com

Yahoo! Groups Links Received on Fri Oct 08 15:45:00 2004

This archive was generated by hypermail 2.1.8 : Mon Oct 27 2008 - 20:24:05 EDT