I reminbered "PSV should be installed vertically" is one statement of API code (or maybe ASME BPC code), but there is not a solid reason why.
I do not see a problem to install a PSV in horizontal position, only "problem" is your piping installation does not agree with the code anymore. If you have no other way to install it, you may want to get approval from client to do it this way.
Thanks
Robert Liu
sandeep manoharan <sandeep.manoharan@eil.co.in> wrote:
thanks for your interest ....
The "generally not" portion is already clear to me but i want to know why ??
>>Generally it is NOT desirable to install PSV-s in horizontal plane.
refer my earlier mail : i have accounted for condensate draining for both the
inlet as well outlet line.
>>In case of condensing vapour lines (e.g. steam), there are chances that
>>condensate may accumulate upstream of the valve during normal operation.
>>When the PSV pops-up, there are chances that there would be severe
>>hammering effect in the entire pipeline. This is typically the reason why
PSV-s >>are installed at the highest point of a pipeline, pipes gradually
>>sloping in either direction
that should not be a problem as my space constraint is mainly because of
structure above hence supporting is not an issue ....... reactive forces in horizontal plane ....... i do not see any problem ...provision of guides / cross guides in the requisite directions should suffice ..........
regards
sandeep
"sandeep manoharan"
01/14/05 09:44 AM
Please respond to PipingDesign
To:
cc:
Subject: Re: [PipingDesign] Query: installation sense of PSV's
.
if you could englighten me & substantiate your reply...... because i believe PSV's being spring loaded should not be faced with that problem ........ ......
thanks in advance ....
sandeep
Check with the PSV vendor.
Typically you can't because the valve will not seat properly after relieving.
sandeep manoharan wrote:
gentle folks....
can PSV's be installed in the Horizontal plane i.e. both inlet & outlet are in
the same horizontal plane. My situation arises because of height & space
restriction.
thanks in advance..
sandeep
[Non-text portions of this message have been removed]
To visit your group on the web, go to:
http://groups.yahoo.com/group/PipingDesign/
To unsubscribe from this group, send an email to: PipingDesign-unsubscribe@yahoogroups.com
Your use of Yahoo! Groups is subject to the Yahoo! Terms of Service.
[Non-text portions of this message have been removed]
Yahoo! Groups Links
[Non-text portions of this message have been removed]
Yahoo! Groups Links
--------------------------------------------------------------------------------\ ---------------------
--------------------------------------------------------------------------------\ -----------------------
[Non-text portions of this message have been removed]
Yahoo! Groups Links
[Non-text portions of this message have been removed]
Yahoo! Groups Links
[Non-text portions of this message have been removed] Received on Fri Jan 14 20:25:00 2005
This archive was generated by hypermail 2.1.8 : Mon Oct 27 2008 - 20:24:06 EDT