Pipe supports

From: <Pankaj.Mandal@fluor.com>
Date: Tue Feb 15 2005 - 00:49:00 EST

As a common practice, pipe supports such as guides and axial stops are modeled in stress analysis software as point contact supports i.e. it restricts movements only and allows free rotation.

It we really go into construction of these supports, in most cases, it locks one or more additional degree of freedom, not accounted for in our analysis.

Let's take an example of a simple pipe guide on shoe, locking movement in say X-axis (let X be north, Z be east and Y - up). If we consider no gap in the pipe support, rotation about Y-axis is also locked. Now my question to all is whether this locked rotation is considered in your analysis.

I did a similar test case for a pipe support near equipment. The result was quite disturbing. Introducing a rotational stop at support point resulted in a huge moment, which surely would not make our structural colleagues happy. On the other hand, if we introduced some gap in the support (which is the most probable case), rotational effect was nullified, but loads on equipment nozzle were increased considerably.

Expert opinion solicited.

Regards,
"A CENTRAL ASIAN FRIEND" Christopher Wright <chrisw@skypoint.com> 02/15/05 10:42 AM
Please respond to PipingDesign

         To:     PipingDesign@yahoogroups.com
         cc:
         Subject:        Re: [PipingDesign] Looking for job as a Piping Designer
/ Draftsman
.

On Feb 14, 2005, at 10:48 PM, Steve McKenzie wrote:

> until you can communicate in an asian language as well as our asian
> friends can communicate in English, I suggest that you tread warily.
I owe a lot of people an apology for that crack. I can't help the fact that I really get spun up by poor writing and bad netiquette, and I won't be so hypocritical as to pretend I don't, but I am sorry I offended more people than those who had it coming.

I will say this. You can skate over to any of the Usenet newsgroups to get an idea of what happens to the signal to noise ratio when people don't observe long-standing standards on netiquette. I really think we need to stay on topic and to quoting properly and reply in readable english, which is the language of the list. Christopher Wright P.E. |"They couldn't hit an elephant at chrisw@skypoint.com | this distance" (last words of Gen.

.......................................| John Sedgwick, Spotsylvania
1864)
http://www.skypoint.com/~chrisw/

PipingOffice - Excel Spreadsheets for Piping Calculations http://www.pipingoffice.us/

Main site: http://www.pipingdesign.com

Yahoo! Groups Links

--------------------------------------------------------------------------------\
---------------------

The information transmitted is intended only for the person or entity to which it is addressed and may contain proprietary, business-confidential and/or privileged material. If you are not the intended recipient of this message you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any action taken in reliance upon this message is prohibited. If you received this in error, please contact the sender and delete the material from any computer. Any views expressed in this message are those of the individual sender and may not necessarily reflect the views of the company.
--------------------------------------------------------------------------------\
-----------------------



[Non-text portions of this message have been removed] Received on Tue Feb 15 00:49:00 2005

This archive was generated by hypermail 2.1.8 : Mon Oct 27 2008 - 20:24:06 EDT