RE: Code Velocity Maximums Plastic Pipe Materials

From: <Steve>
Date: Thu Aug 18 2005 - 15:38:00 EDT


Howdy
Cant help you with a Code upper limit (AWWA may be worth a look)but note you make mention of building services. For building services, we normally run a little larger than the economic diameter for reasons of (among others) noise control. If you are looking at high velocities in a building, look carefully at noise requirements as they can bite; I got bitten by a library. The problems of water hammer and pressure regulation you will already be aware of. I am currently running some PE gravity mains at 4.5 - 5 m/s (have head to burn, but flows arent large enough to justify any form of regeneration)without problems, but there are no valves or branches.

Cheers

Steve

-----Original Message-----
From: <a href="/group/PipingDesign/post?postID=6o50EbeImHnt32hnVDXRuvQQl5m51OJt1ooCkAAyg_0ilaul3741S0QRZF0qu5TgshYkvAggHigNvKZ89krlRgdn">PipingDesign@yahoogroups.com</a> [mailto:<a href="/group/PipingDesign/post?postID=6o50EbeImHnt32hnVDXRuvQQl5m51OJt1ooCkAAyg_0ilaul3741S0QRZF0qu5TgshYkvAggHigNvKZ89krlRgdn">PipingDesign@yahoogroups.com</a>] On Behalf Of blenrayaust
Sent: Thursday, August 18, 2005 7:52 PM
To: <a href="/group/PipingDesign/post?postID=6o50EbeImHnt32hnVDXRuvQQl5m51OJt1ooCkAAyg_0ilaul3741S0QRZF0qu5TgshYkvAggHigNvKZ89krlRgdn">PipingDesign@yahoogroups.com</a> Subject: [PipingDesign] Code Velocity Maximums Plastic Pipe Materials

Please advise what Code limits there are for the use of plastic pipe materials in building services. I am not looking for generalisations or manufacturers ideas but hard and fast clauses that may appear in a specification.

The situation I have is where energy costs a fraction of what it does in the USA and therefore the NPV of Capex and Opex is different. So generalisations of maximum velocites are meaningless.



PipingOffice - Excel Spreadsheets for Piping Calculations
<a href="http://www.pipingoffice.us/">http://www.pipingoffice.us/</a> =========================================
Main site: <a href="http://www.pipingdesign.com">http://www.pipingdesign.com</a>

Yahoo! Groups Links

--
No virus found in this incoming message.
Checked by AVG Anti-Virus.
Version: 7.0.338 / Virus Database: 267.10.12/75 - Release Date:
8/17/2005
Received on Thu Aug 18 15:38:00 2005

This archive was generated by hypermail 2.1.8 : Tue Mar 04 2008 - 11:40:43 EST