RE: Code Velocity Maximums Plastic Pipe Materials

From: <Geoff>
Date: Thu Aug 18 2005 - 17:20:00 EDT


Steve,

AS 3500.1.2 Plumbing and Drainage Code for Australia and New Zealand has an upper limit of 3 m/s (refer clause 3.4)

Geoff

Steve McKenzie <Mechproj@xtra.co.nz> wrote: Howdy
Cant help you with a Code upper limit (AWWA may be worth a look)but note you make mention of building services. For building services, we normally run a little larger than the economic diameter for reasons of (among others) noise control. If you are looking at high velocities in a building, look carefully at noise requirements as they can bite; I got bitten by a library. The problems of water hammer and pressure regulation you will already be aware of. I am currently running some PE gravity mains at 4.5 - 5 m/s (have head to burn, but flows arent large enough to justify any form of regeneration)without problems, but there are no valves or branches.

Cheers

Steve

-----Original Message-----
From: <a href="/group/PipingDesign/post?postID=7Haq8dY7r2bWTamj67ZOq1VnQYcvkGmJXUoXk84ROCdgausQH9NKIdVkNzAhx9-BdPsUxwTC_6DUiQskW-5TzxBvLQ">PipingDesign@yahoogroups.com</a> [mailto:<a href="/group/PipingDesign/post?postID=7Haq8dY7r2bWTamj67ZOq1VnQYcvkGmJXUoXk84ROCdgausQH9NKIdVkNzAhx9-BdPsUxwTC_6DUiQskW-5TzxBvLQ">PipingDesign@yahoogroups.com</a>] On Behalf Of blenrayaust
Sent: Thursday, August 18, 2005 7:52 PM
To: <a href="/group/PipingDesign/post?postID=7Haq8dY7r2bWTamj67ZOq1VnQYcvkGmJXUoXk84ROCdgausQH9NKIdVkNzAhx9-BdPsUxwTC_6DUiQskW-5TzxBvLQ">PipingDesign@yahoogroups.com</a> Subject: [PipingDesign] Code Velocity Maximums Plastic Pipe Materials

Please advise what Code limits there are for the use of plastic pipe materials in building services. I am not looking for generalisations or manufacturers ideas but hard and fast clauses that may appear in a specification.

The situation I have is where energy costs a fraction of what it does in the USA and therefore the NPV of Capex and Opex is different. So generalisations of maximum velocites are meaningless.



PipingOffice - Excel Spreadsheets for Piping Calculations
<a href="http://www.pipingoffice.us/">http://www.pipingoffice.us/</a> =========================================
Main site: <a href="http://www.pipingdesign.com">http://www.pipingdesign.com</a>

Yahoo! Groups Links

--
No virus found in this incoming message.
Checked by AVG Anti-Virus.
Version: 7.0.338 / Virus Database: 267.10.12/75 - Release Date:
8/17/2005





=========================================
PipingOffice - Excel Spreadsheets for Piping Calculations <a href="http://www.pipingoffice.us/">http://www.pipingoffice.us/</a>
=========================================
Main site: <a href="http://www.pipingdesign.com">http://www.pipingdesign.com</a> --------------------------------- YAHOO! GROUPS LINKS Visit your group "PipingDesign" on the web. To unsubscribe from this group, send an email to: <a href="/group/PipingDesign/post?postID=PE2JOYxxhuuiWy0u2QY4zj6by8u1N7PUqwS-_sgjzGmE0yBtj7dyVkaNnhM9qSGHrJb0qa83w1caUg-MhDVGaWi_NGhaaKIZufWv6hyj">PipingDesign-unsubscribe@yahoogroups.com</a> Your use of Yahoo! Groups is subject to the Yahoo! Terms of Service. --------------------------------- Design Detail and Development (a division of Blenray Pty Ltd) Mail Address PO Box 1351 Castle Hill NSW 1765 Australia Tel Mob 0402 35 2313 Office 02 8850 2313 AH 02 8850 2324 We specialise in pipe network and waterhammer analysis, pipe stress analysis, the design of buried pipelines and thermoplastic pipe systems. [Non-text portions of this message have been removed]
Received on Thu Aug 18 17:20:00 2005

This archive was generated by hypermail 2.1.8 : Tue Mar 04 2008 - 11:40:43 EST