Randy,
"gi" is a common description in SE Asia and the sub continent for galvanised iron. Left over from the British Raj. Even though it is galvanised steel now it is still referred to as "gi".
The fact is most have moved away from gi and use modern thermoplastics like ABS, PP, UpVC, PE etc.
Geoff
Geoff
"Conner, Randy" <RConner@acipco.com> wrote:
Is it possible this is meant to be a sort of mechanical "Gibault"-type joint
(or mechanical joint collar or sleeve?) Such a structure, similar to a flanged
adapter(or) or Dresser/Smith-Blair et al coupling, would allow "drop-in" (or
pull out) assembly (or disassembly) e.g. between flanges (see also the last
fitting, the "collar" at the site
http://www.acipco.com/international/products/Sec10.pdf. It should be noted that
just a mechanical sleeve per se between flanges would not however provide
longitudinal restraint to a system, if this was necessary in the application (so
rods across flanges or other restraint would have to be provided, if restraint
is needed). Special mechanically joined structures sometimes referred to as
"dismantling joints" or restrained flange adapters often contain restraint
features in the devices. You could perhaps do an internet search with the help
of these terms for more information, if this doesn't "hit it".
Randy Conner
Research Department - Technical Division
American Cast Iron Pipe Company
1501 31st Avenue North, Birmingham, AL 35207
P. O. Box 2727, Birmingham, AL 35202
ph 205-325-7946
fax 205-325-8095
-----Original Message-----
From: PipingDesign@yahoogroups.com
[mailto:PipingDesign@yahoogroups.com]On Behalf Of Singh AnilKumar SPEL
Sent: Monday, January 16, 2006 1:15 AM
To: PipingDesign@yahoogroups.com
Subject: [PipingDesign] gi bolt type joint.
Hello piping experts,
Can anybody tell me something about gi bolt type joint. This is a case
of flanged spool piece( 500 mm) between two fixed flanged ends in the
water pipe.
For removal of gasket the above type of joint is recommended. If someone
can give some details/ information than it will be a great help.
Thanks & regards
Anil Singh
SIEMENS Power Engineering (P) Ltd.
Plot No. 6A, Sector-18, Maruti Industrial
Area, Gurgaon - 122015, Haryana.
*Tel.: ++95124-2842009
Fax. . ++91-124-2347512
*Mail: anilkumar.singh@siemens.com
[Non-text portions of this message have been removed]
Yahoo! Groups Links
_________Confidentiality Notice_______________________This e-mail and any files transmitted with it is confidential and is intended solely for the use of the individual(s) or entity(ies) to whom this e-mail is addressed. If you are not the intended recipient or the person responsible for delivering the e-mail to the intended recipient, be advised that you have received this e-mail in error, and that any use, disclosure, dissemination, forwarding, printing, retention or copying of this e-mail is strictly prohibited. If you have received this e-mail in error, please immediately return this e-mail to the sender and delete the e-mail from your system. Thank you.
SPONSORED LINKS
Mechanical engineering Mechanical engineering jobs Cad drafter
Process piping Mechanical
YAHOO! GROUPS LINKS Visit your group "PipingDesign" on the web.
To unsubscribe from this group, send an email to: PipingDesign-unsubscribe@yahoogroups.com
Your use of Yahoo! Groups is subject to the Yahoo! Terms of Service.
Design Detail and Development (a division of Blenray Pty Ltd)
Mail Address PO Box 1351 Castle Hill NSW 1765 Australia Tel Mob 0402 35 2313
Office 02 8850 2313 AH 02 8850 2324
We specialise in pipe network and waterhammer analysis, pipe stress analysis,
the design of buried pipelines and thermoplastic pipe systems.
[Non-text portions of this message have been removed] Received on Mon Jan 16 16:58:00 2006