Shabbir:
If the chlorine (as in all forms) will all stay INSIDE the pipe, then there is no need to use coatings or exotic metals for supports or fittings. If there are sources of leaks (pump seals, open tanks, agitator seals, etc.), then, because chlorine/chlorides are very corrosive, that must be taken into consideration. I would still consider using painted or galvanized carbon steel, unless there is potential for liquid leakages.
... Bruce D. Bullough ...
Lead Process Engineer
Foth Production Systems, LLC
8550 Hudson Boulevard North, Suite 100
Lake Elmo, MN 55042
Direct: +651-288-8598 Fax: +651-288-8551
http://www.foth.com
IMPORTANT NOTICE
This communication including any attachments, (E-mail) is confidential and
may be proprietary, privileged or otherwise protected from disclosure. If
you are not the intended recipient, please notify the sender, permanently
delete this E-mail from your system and destroy any copies. Any use of
the E-mail, including disclosure, distribution or replication, by someone
other than its intended recipient is prohibited.
This E-mail has the potential to have been altered or corrupted due to transmission or conversion. It may not be appropriate to rely upon this E-mail in the same manner as hard copy materials bearing the author's original signature or seal.
Hello Everybody,
Presently I am working on a Sodium Hypochloride service line. As I know
that
we because of the stress corrosion cracking we cannot use Austinite Steel
for this service, line size is 1" to 1 1/2", we planned to use stainless
steel support and with U bolt. Please guide me whether this support
require
any coating like titanium including U bolt please explain me this.
Thanks and have a nice DAY.
Shabbir Ahmed
Received on Thu Nov 08 08:48:00 2007