Thank you very much, Bruce.
My concern is that: wouldnt that threaded instrument
connection make the line threaded one?
How should we explain the case?
Hope you understand my query.
Regards
Amjad
> Amjad - Normally a reference to threaded connections
> for instrumentation
> in a piping spec is in reference to pressure sensing
> instruments (
> including flow instruments) - which ape provided
> with male npt
> connections. The piping system will include a "root
> valve" which will have
> a connection per piping spec ( socket welded for
> example) on one side & a
> female threaded connection on the other side where
> direct mounting of a
> threaded instrument or the installation of a
> threaded tubing adaptor which
> will connect to a remote mounted instrument is
> possible. Take a look at
> your instrumentation department's standard
> installation details - normally
> a reference is made to differentiate between the
> piping & instrumentation
> disciplines -
> Is this your case?
> Bruce R. Raymond
> Senior Design Supervisor
> Fluor
>
________________________________________________________________________________\
This archive was generated by hypermail 2.1.8 : Tue Mar 09 2010 - 00:21:23 EST